Performance assessment of an experimental CO2 transcritical refrigeration plant working with a thermoelectric subcooler in combination with an internal heat exchanger
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Casi, Álvaro; Aranguren, Patricia; Araiz, Miguel; Sánchez García-Vacas, Daniel; Cabello López, Ramón; Astrain, David
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
Performance assessment of an experimental CO2 transcritical refrigeration plant working with a thermoelectric subcooler in combination with an internal heat exchangerAutoría
Fecha de publicación
2022-07-19Editor
ElsevierCita bibliográfica
CASI, Álvaro, et al. Performance assessment of an experimental CO2 transcritical refrigeration plant working with a thermoelectric subcooler in combination with an internal heat exchanger. Energy Conversion and Management, 2022, vol. 268, p. 115963.Tipo de documento
info:eu-repo/semantics/articleVersión
info:eu-repo/semantics/publishedVersionPalabras clave / Materias
Resumen
Regulations in the refrigeration sector are forcing the transition to low global warming potential fluids such as carbon dioxide in order to decrease direct greenhouse gases emissions. Several technologies have arisen ... [+]
Regulations in the refrigeration sector are forcing the transition to low global warming potential fluids such as carbon dioxide in order to decrease direct greenhouse gases emissions. Several technologies have arisen over the past years to compensate the low performance of the transcritical carbon dioxide vapour compression cycle at high ambient temperatures. For low–medium power units, the inclusion of a thermoelectric subcooler or an internal heat exchanger have been proven as effective solutions for enhancing the coefficient of performance. However, the combination of a thermoelectric subcooler and an internal heat exchanger working simultaneously is yet to be explored theoretically or experimentally. This work presents, for the first time, an experimental transcritical carbon dioxide refrigeration facility that works simultaneously with a thermoelectric subcooler and with an internal heat exchanger in order to boost the cooling capacity and coefficient of performance of the refrigeration system. The experimental tests report improvements at optimum working conditions of 22.4 % in the coefficient of performance and an enhancement in the cooling capacity of 22.5 %. The 22.4 % increase in coefficient of performance would result in a decrease of energy consumption along a reduction of the greenhouse gases emissions. The proposed combination of a thermoelectric subcooler and an internal heat exchanger outperforms each of the technologies on their own and presents itself as a great controllable solution to boost the performance and reduce the greenhouse gasses emissions of transcritical carbon dioxide refrigeration cycles. [-]
Publicado en
Energy Conversion and Management, Volume 268, September 2022Entidad financiadora
Ministerio de Ciencia, Innovación y Universidades (Spain) | European Regional Development Fund. | Government of Navarra. Education Department (Spain) | Universidad Pública de Navarra | Official School of Industrial Engineers of Navarre (Spain)
Código del proyecto o subvención
RTI2018-093501-B-C21 | RTI2018-093501-B-C22