Space vector (SV)-based estimation algorithms represent attractive methods for synchronized phasor, frequency, and rate of change of frequency measurements in three-phase ac power systems. Recently, a phase-locked-loop (PLL) solution for improving the demodulation of the SV signal has been proposed. In this article, the potentialities of the SV-PLL approach are investigated in order to optimize accuracy and computational load. First, the impact of the PLL update rate on achieved performance is analyzed. Then, a novel two-step SV-PLL algorithm is presented so that the accuracy of a fast PLL execution frequency can be matched with a considerably lower computational cost. The behavior in the case of fast phase angle variations has been also significantly improved. The proposed synchrophasor estimation technique has been validated through simulations; exemplary dynamic performance suggests that it is particularly suitable for grid control applications. Experimental tests carried out on a real-time implementation confirm simulation results.

Proposals and Analysis of Space Vector-Based Phase-Locked-Loop Techniques for Synchrophasor, Frequency, and ROCOF Measurements

Pegoraro P. A.;
2020-01-01

Abstract

Space vector (SV)-based estimation algorithms represent attractive methods for synchronized phasor, frequency, and rate of change of frequency measurements in three-phase ac power systems. Recently, a phase-locked-loop (PLL) solution for improving the demodulation of the SV signal has been proposed. In this article, the potentialities of the SV-PLL approach are investigated in order to optimize accuracy and computational load. First, the impact of the PLL update rate on achieved performance is analyzed. Then, a novel two-step SV-PLL algorithm is presented so that the accuracy of a fast PLL execution frequency can be matched with a considerably lower computational cost. The behavior in the case of fast phase angle variations has been also significantly improved. The proposed synchrophasor estimation technique has been validated through simulations; exemplary dynamic performance suggests that it is particularly suitable for grid control applications. Experimental tests carried out on a real-time implementation confirm simulation results.
2020
Current measurement; frequency measurement; phase-locked loops (PLLs); phasor measurement units (PMUs); power distribution; power transmission; synchrophasor estimation; three-phase systems; voltage measurement
File in questo prodotto:
File Dimensione Formato  
08998169.pdf

Solo gestori archivio

Descrizione: editorial version
Tipologia: versione editoriale
Dimensione 1.87 MB
Formato Adobe PDF
1.87 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11584/292827
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 10
  • ???jsp.display-item.citation.isi??? 8
social impact