Abstract
A model co-relating the peak load demand of a utility with the allowable power rating (PR) of air-conditioning (AC) systems has been developed in this paper through a well defined methodology. The model is capable to predict the extent of allowable increase in the capital cost of the AC system for an improvement in PR from its base case as well. Furthermore, effectiveness of better PR of AC system for peak load management has been analyzed for Kuwait as a case study. It is found that up to 5,752 MW in reduction in peak load demand and savings of KD 2,301 million in capital expenditures are possible for the years between 2001 and 2025 if the PR of AC systems are improved to 1.2 kW/RT from its present level of 2.0 kW/RT. Also, it is estimated that extent of increase in capital cost of AC system by 106 % is justified for reducing the expenditure for new power plants. The paper will be useful for the energy planner and policy makers in the countries of Arabian Peninsula with huge demand for air-conditioning.
Citation