NASA Logo

NTRS

NTRS - NASA Technical Reports Server

Back to Results
Evaluation of initial collector field performance at the Langley Solar Building Test FacilityThe thermal performance of the solar collector field for the NASA Langley Solar Building Test Facility is given for October 1976 through January 1977. A 1,180 square meter solar collector field with seven collector designs helped to provide hot water for the building heating system and absorption air conditioner. The collectors were arranged in 12 rows with nominally 51 collectors per row. Heat transfer rates for each row were calculated and recorded along with sensor, insolation, and weather data every five minutes using a minicomputer. The agreement between the experimental and predicted collector efficiencies was generally within five percentage points.
Document ID
19770019673
Acquisition Source
Legacy CDMS
Document Type
Conference Paper
Authors
Boyle, R. J.
(NASA Lewis Research Center Cleveland, OH, United States)
Jensen, R. N.
(NASA Langley Hampton, Va., United States)
Knoll, R. H.
(NASA Lewis Research Center Cleveland, OH, United States)
Date Acquired
September 3, 2013
Publication Date
June 1, 1977
Subject Category
Energy Production And Conversion
Report/Patent Number
NASA-TM-X-73677
Accession Number
77N26617
Distribution Limits
Public
Copyright
Work of the US Gov. Public Use Permitted.
No Preview Available