Performance evaluation of natural ventilation strategies for hospital wards: case study of Great Ormond Street Hospital

Download (409.46 kB)
journal contribution
posted on 2013-02-04, 15:32 authored by Zulfikar Adamu, Andrew Price, Malcolm CookMalcolm Cook
Natural ventilation is attractive due its potential to lower energy consumed by healthcare environments but maintaining steady/adequate airflow rates and thermal comfort is challenging in temperate countries. Although many contemporary hospitals use traditional windows for natural ventilation, there are alternative strategies that are largely under-utilised probably due to lack knowledge of their ventilation performances. Each alternative has design implications and airflow characteristics – both of which affect thermal comfort and heating energy. This study evaluates the performance of buoyancy-driven airflows through four selected natural ventilation strategies suitable for single-bed hospital wards. These strategies are: single window opening, same side dual-opening, inlet and stack as well as ceiling-based natural ventilation (CBNV), a new concept. These strategies have been explored via dynamic thermal simulation and computational fluid dynamics, using a new ward of the Great Ormond Street Hospital (GOSH) London as a case study. Results reveal that 25% trickle ventilation opening fraction is required to achieve required airflow rates and acceptable thermal comfort in winter, and with exception of window-based design, other strategies minimise summer overheating to different extents. The CBNV concept uniquely shields fresh air and delivers it to isolated parts of wards or directly over patients (i.e. personalisation). This provides higher air quality at such locations and creates mixing which aids comfort and dilution. The findings demonstrate how quantitative data from simulations can be used by designers to meet qualitative or sensory design objectives like airflow direction and thermal comfort with respect to the energy consumed in space and time.

History

School

  • Architecture, Building and Civil Engineering

Citation

ADAMU, Z.A., PRICE, A.D.F. and COOK, M.J., 2012. Performance evaluation of natural ventilation strategies for hospital wards: case study of Great Ormond Street Hospital. Building and Environment, 56, pp.211-222.

Publisher

© Elsevier

Version

  • AM (Accepted Manuscript)

Publication date

2012

Notes

This is the author’s version of a work that was accepted for publication in the journal Building and Environment. Changes resulting from the publishing process, such as peer review, editing, corrections, structural formatting, and other quality control mechanisms may not be reflected in this document. Changes may have been made to this work since it was submitted for publication. A definitive version was subsequently published at:

ISSN

0360-1323

Language

  • en